Tuesday, February 21, 2012

sensors in IBM Lab


sensors in A13

PH.VAV.RMA13.ROOM TEMP (Room Temperature Sensor) [I/O time out]
Porter Hall. A level. A13.Airflow (Airflow sensor) [400]
Porter Hall. A level. A13.CLG Flow Max (Cooling flow maximum value) [ 640]
Porter Hall. A level. CLG Flow Min (Cooling flow minimum value) [ 400]
Porter Hall.A level. Control Setpoint (Control Setpoint) [73]
Porter Hall. A level.A13.Control Temperature (Control Temperature)[72.75]
Porter Hall. A level. A13. Damper Command (Damper Command) [37.6]
Porter Hall. A level. A13. Damper Status (Damper Status) [0]
Porter Hall. A level. A13. Day CLG Setpoint (Day cooling Set point)[74]
Porter Hall. A level. A13. Day HTG Setpoint (Day Heating Set point)[70]
Porter Hall. A level. A13. Day.Night (Day/Night Value)[0]
Porter Hall. A level. A13. DI OVRD SW (Status of the override switch at the room temp sensor) [0]
Porter Hall.A level. A13.Discharge Temp (Discharge Temp) [71]
Porter Hall.A level. A13.Duct Area (Duct Area) [0.55]
Porter Hall.A level. A13.Error Status (Error Status) [0]
Porter Hall.A level. A13.Flow (Flow) [100]
Porter Hall.A level. A13. Flow Coeff (Flow Coefficient) [0.65]
Porter Hall.A level. A13. Flow End (Flow End) [100]
Porter Hall.A level. A13.Flow Setpoint (Flow Setpoint) [100]
Porter Hall.A level. A13.Flow Start (Flow Start)[0]
Porter Hall.A level. A13.Heat. Cool [1]
Porter Hall.A level. A13.HTG Flow Max (Heating Flow Max) [400]
Porter Hall.A level. Area13. HTG Flow Min (Heating Flow Min) [400]
Porter Hall.A level. A13.MTR Setup (Motor Setup) [5]
Porter Hall.A level. A13.MTR2 Timing (Motor 2 Timing)[130]
Porter Hall.A level. A13.Night CLG Setpoint (Night Cooling Set point)[82]
Porter Hall.A level. A13.NIght HTG Setpoint (Night Heating Set point)[65]
Porter Hall.A level. A13.Night OVRD (Night  Override)[1]
Porter Hall.A level. A13.NIght OVRD Time( Night Override Time)[0]
Porter Hall.A level. A13.Reheat End (Reheat End)[100]
Porter Hall.A level. A13.Reheat Start (Reheat Start)[0]
Porter Hall.A level. A13.Setpoint DIAL (Setpoint Dial)[1]
Porter Hall.A level. A13.Valve Command (Valve Command)[1]
Porter Hall.A level. A13.Valve Count (Valve Count)[0]
Porter Hall.A level. A13.Valve Position (Valve Position)[0]
Porter Hall.A level. A13.Wall Switch (Wall Switch)[0]
Porter Hall.A level. A13.Zone Temp (Zone Temp)[72.75]
Porter Hall.A level. A13.Zone Temp Offset (Zone Temp Offset)[0]
Porter Hall.A level. A13.ZOne Temp Setpoint (Zone Temp Setpoint)[73]
Porter Hall.A level. A13.Zone Temp Setpoint Max (Zone Temp Setpoint max)[90]
Porter Hall.A level. A13.Zone Temp Setpoint Min (ZOne Temp Setpoint min)[55]

sensors in A15
Porter Hall. A level. A15.Airflow (Airflow sensor) [404]
Porter Hall. A level. A15.CLG Flow Max (Cooling flow maximum value) [740]
Porter Hall. A level. A.15CLG Flow Min (Cooling flow minimum value) [ 400]
Porter Hall.A level. A15.Control Setpoint (Control Setpoint) [74.25]
Porter Hall. A level.A15.Control Temperature (Control Temperature)[74.75]
Porter Hall. A level. A15. Damper Command (Damper Command) [40.4]
Porter Hall. A level. A15. Damper Status (Damper Status) [0]
Porter Hall. A level. A15. Day CLG Setpoint (Day cooling Set point)[74]
Porter Hall. A level. A15. Day HTG Setpoint (Day Heating Set point)[70]
Porter Hall. A level. A15. Day.Night (Day/Night Value)[0]
Porter Hall. A level. A15. DI OVRD SW (Status of the override switch at the room temp sensor) [0]
Porter Hall.A level. A15.Discharge Temp (Discharge Temp) [75]
Porter Hall.A level. A15.Duct Area (Duct Area) [0.55]
Porter Hall.A level. A15.Error Status (Error Status) [0]
Porter Hall.A level. A15.Flow (Flow) [101]
Porter Hall.A level. A15. Flow Coeff (Flow Coefficient) [0.65]
Porter Hall.A level. A15. Flow End (Flow End) [0]
Porter Hall.A level. A15.Flow Setpoint (Flow Setpoint) [100]
Porter Hall.A level. A15.Flow Start (Flow Start)[0]
Porter Hall.A level. A15.Heat. Cool [1]
Porter Hall.A level. A15.HTG Flow Max (Heating Flow Max) [400]
Porter Hall.A level. A15. HTG Flow Min (Heating Flow Min) [400]
Porter Hall.A level. A15.MTR Setup (Motor Setup) [5]
Porter Hall.A level. A15.MTR2 Timing (Motor 2 Timing)[130]
Porter Hall.A level. A15.Night CLG Setpoint (Night Cooling Set point)[82]
Porter Hall.A level. A15.NIght HTG Setpoint (Night Heating Set point)[65]
Porter Hall.A level. A15.Night OVRD (Night  Override)[1]
Porter Hall.A level. A15.NIght OVRD Time( Night Override Time)[0]
Porter Hall.A level. A15.Reheat End (Reheat End)[100]
Porter Hall.A level. A15.Reheat Start (Reheat Start)[0]
Porter Hall.A level. A15.Setpoint DIAL (Setpoint Dial)[1]
Porter Hall.A level. A15.Valve Command (Valve Command)[0]
Porter Hall.A level. A15.Valve Count (Valve Count)[1]
Porter Hall.A level. A15.Valve Position (Valve Position)[0]
Porter Hall.A level. A15.Wall Switch (Wall Switch)[0]
Porter Hall.A level. A15.Zone Temp (Zone Temp)[74.25]
Porter Hall.A level. A15.Zone Temp Offset (Zone Temp Offset)[0]
Porter Hall.A level. A15.ZOne Temp Setpoint (Zone Temp Setpoint)[74.25]
Porter Hall.A level. A15.Zone Temp Setpoint Max (Zone Temp Setpoint max)[90]
Porter Hall.A level. A15.Zone Temp Setpoint Min (ZOne Temp Setpoint min)[55]


sensors in A17

Porter Hall.A level. A17.Airflow (Airflow sensor) [452]
Porter Hall.A level. A17.CLG Flow Max (Cooling flow maximum value) [452]
Porter Hall.A level. A.17.CLG Flow Min (Cooling flow minimum value) [ 452]
Porter Hall.A level. A17.Control Setpoint (Control Setpoint) [73]
Porter Hall.A level.A17.Control Temperature (Control Temperature)[72.75]
Porter Hall.A level. A17. Damper Command (Damper Command) [53.2]
Porter Hall.A level. A17. Damper Status (Damper Status) [0]
Porter Hall.A level. A17. Day CLG Setpoint (Day cooling Set point)[74]
Porter Hall.A level. A17. Day HTG Setpoint (Day Heating Set point)[70]
Porter Hall.A level. A17. Day.Night (Day/Night Value)[0]
Porter Hall.A level. A17. DI OVRD SW (Status of the override switch at the room temp sensor) [0]
Porter Hall.A level. A17.Discharge Temp (Discharge Temp) [71]
Porter Hall.A level. A17.Duct Area (Duct Area) [0.375]
Porter Hall.A level. A17.Error Status (Error Status) [0]
Porter Hall.A level. A17.Flow (Flow) [100]
Porter Hall.A level. A17. Flow Coeff (Flow Coefficient) [0.54]
Porter Hall.A level. A17. Flow End (Flow End) [0]
Porter Hall.A level. A17.Flow Setpoint (Flow Setpoint) [100]
Porter Hall.A level. A17.Flow Start (Flow Start)[0]
Porter Hall.A level. A17.Heat. Cool [1]
Porter Hall.A level. A17.HTG Flow Max (Heating Flow Max) [452]
Porter Hall.A level. A17. HTG Flow Min (Heating Flow Min) [452]
Porter Hall.A level. A17.MTR Setup (Motor Setup) [13]
Porter Hall.A level. A17.MTR2 Timing (Motor 2 Timing)[130]
Porter Hall.A level. A17.Night CLG Setpoint (Night Cooling Set point)[82]
Porter Hall.A level. A17.NIght HTG Setpoint (Night Heating Set point)[65]
Porter Hall.A level. A17.Night OVRD (Night  Override)[1]
Porter Hall.A level. A17.NIght OVRD Time( Night Override Time)[0]
Porter Hall.A level. A17.Reheat End (Reheat End)[100]
Porter Hall.A level. A17.Reheat Start (Reheat Start)[0]
Porter Hall.A level. A17.Setpoint DIAL (Setpoint Dial)[1]
Porter Hall.A level. A17.Valve Command (Valve Command)[0]
Porter Hall.A level. A17.Valve Count (Valve Count)[1]
Porter Hall.A level. A17.Valve Position (Valve Position)[0]
Porter Hall.A level. A17.Wall Switch (Wall Switch)[0]
Porter Hall.A level. A17.Zone Temp (Zone Temp)[72.75]
Porter Hall.A level. A17.Zone Temp Offset (Zone Temp Offset)[0]
Porter Hall.A level. A17.ZOne Temp Setpoint (Zone Temp Setpoint)[73]
Porter Hall.A level. A17.Zone Temp Setpoint Max (Zone Temp Setpoint max)[90]
Porter Hall.A level. A17.Zone Temp Setpoint Min (Zone Temp Setpoint min)[55]



There is some bacnet stuff in A17/15 like follows but I dont know if they are meaningful
BACnet_PORTERPXCM01_PH.AHU.RMA17D..VAV.HWF (Variable Air Volume Hot water supply flow ) [5.97]
BACnet_PORTERPXCM01_PH.AHU.RMA17D..VAV.HWF.2 (Variable Air Volume Hot water supply flow ) [5.1050]
BACnet_PORTERPXCM01_PH.AHU.RMA17D..VAV.HWF.PRESENT VALUE (Variable Air Volume Hot water supply flow Present Value ) [5.0825]
BACnet_PORTERPXCM01_PH.AHU.RMA17D.CCV (Chilled Water Valve Signal)[7.43]
BACnet_PORTERPXCM01_PH.AHU.RMA17D.CCV.2(Chilled Water Valve Signal)[3.55]
BACnet_PORTERPXCM01_PH.AHU.RMA17D.CCV.PRESENT VALUE (Chilled Water Valve Signal)[7.488]

BACnet_PORTERPXCM01_PH.AHU.RMA17D.CC(Chilled Water Valve CMD)[74.52%]
BACnet_PORTERPXCM01_PH.AHU.RMA17D.CC_.2(Chilled Water Valve CMD)[36.26%]
BACnet_PORTERPXCM01_PH.AHU.RMA17D.CC_.Present_Value(Chilled Water Valve CMD)[74.52%]